[technical analysis] causes of high surface temperature of water cooled condenser

visits:41 addtime:2023-10-11 16:37:33

n the working process of the refrigeration system, the temperature of the outer surface of the water-cooled stage condenser should be close to the normal temperature, and the hands should not feel hot. Once the surface temperature is too high, the cause should be found out and measures should be taken to eliminate this phenomenon.


Generally speaking, the main cause of condenser temperature rise is the problem of cooling water. There are usually four kinds of feelings


Situation:


1) There is not enough cooling water and water pressure. The water-cooled condenser uses cooling water to take away the latent heat released during the condensation of refrigerant vapor. Therefore, the pressure of cooling water is not enough, the flow rate can not meet the rated requirements, and the heat dissipation capacity is limited, * which eventually causes the surface temperature of the condenser to rise.


2) The cooling water temperature is too high, which is higher than the rated operating temperature (usually 32 ℃). The cooling water temperature in Vietnam, the smaller the cooling temperature difference of refrigerant, the smaller the heat transfer, the refrigerant can not be effectively cooled, and the surface temperature of condenser will rise


High.


3) The poor quality of cooling water leads to scaling on the inner wall of the cooling water pipe in the condenser, increasing the thermal resistance, affecting the heat exchange between refrigerant and cooling water, and reducing the heat transfer effect. This kind of fault often occurs in the equipment which has been used for a long time and has not been cleaned regularly. The solution is to remove scale.


4) The inlet and outlet pipes of cooling water are installed incorrectly. The normal installation position is generally low inlet pipe position and high outlet pipe position


"Low in, high out.". If the inlet pipe is set high, the cooling water can not be completely filled in the condenser, the heat transfer area will be smaller, and the refrigerant vapor can not be effectively condensed, which will make the surface temperature of the condenser rise.


When the surface temperature of the condenser increases, it means that the condensation effect is recommended, and the cooling capacity of the system will decrease.


<menuitem id="uv949"></menuitem>
  • <menuitem id="uv949"><center id="uv949"><em id="uv949"></em></center></menuitem>
        主站蜘蛛池模板: 五个姿势夹到男人爽| 欧美在线人视频在线观看| 奷小罗莉在线观看国产| 人妻熟女在线制服丝袜在线| 汤阴县| 漂亮老师做爰8| 日韩精品极品视频在线观看免费| 镇沅| 醴陵市| 扶绥县| 金乡县| 南平市| 国产AⅤ爽AV久久久久成人社区| 九江县| 小荡货女友小怡H调教H文| 成人精品一区二区三区电影| 萝北县| 韩国电影按摩的清爽基础油| 日本看片一二三区高清| 特级毛片片A片AAAAAA| 阜宁县| 日出水了啊快点使劲| 久女女热精品视频在线观看| 在线观看特色大片免费网站 | 崇明县| 将军边走边挺进她H树林| 好爽毛片一区二区三区**| 真人作爱90分钟免费看视频 | 镇原县| 公车全黄H全肉短篇公车之狼| 欧美肥老太牲交| 日本免费最新高清不卡视频 | 精品国产精品人妻久久无码五月天| 白水县| 久9re热视频这里只有精品| 欧美香蕉爽爽人人爽| 佛学| 绩溪县| 贡觉县| 诱人的老师7HD中字| 日本av不卡在线观看|